Thermodynamic and exergy analysis of thermal System
Loading...
Date
item.page.authors
Journal Title
Journal ISSN
Volume Title
Publisher
Abstract
In the thesis, the refrigeration and air-conditioning systems having low carbon emission
newlineand eco-friendly relationship have been examined and evaluated. An attempt has been
newlinemade to synthesise the vapour compression and absorption cycles for the investigation of
newlineenergy and exergy performance.
newlineThe subcooling methods viz. liquid vapour heat exchanger incorporation to vapour
newlinecompression refrigeration (VCR) system and dedicated mechanical subcooled VCR
newlinesystem have been investigated using R134a and alternate refrigerants R1234yf and
newlineR1234ze. An experimental VCR setup has also compared to simple theoretical VCR
newlinesystem in order to examine the performance and compatibility of alternative refrigerants.
newlineThe results depict that the subcooling methods improve coefficient of performance (COP)
newlineand exergy efficiency of the VCR system. The performance of R1234ze is better than that
newlineof R1234yf and it competes with R134a.
newlineThe low grade energy (waste heat) available at temperature (i.e. within 60-2000C) is
newlineutilized as source in the various cascade configurations of vapour compressionabsorption
newlinerefrigeration cycles. The objectives of the present work are reduction in high
newlinegrade energy (electrical energy) consumed by the compressor consequently, reduction in
newlinecarbon emission and global warming potential. Simultaneously, the cascading effect
newlineproduces lower temperature for the deep freezing and chilling applications.
newlineFor achieving the dual objectives, the energy and exergy analysis of absorptioncompression
newlinecascade refrigeration cycles along with wide range of parametric analysis
newlinehave been carried out by developing engineering equation solver (EES) software based
newlinecomputer programs.
newlineThe waste heat available at higher temperature (165-2000C) has been utilized in
newlinecompression-absorption (triple effect series flow H2O-LiBr) cascade refrigeration cycle
newlinewhile the low temperature (65-950C) waste heat has been utilized in compression absorption
newline(single and half effect series flow H2O-LiBr) cascade refrigeration cycle.